NAPCO Gemini C-Series Control Panel Programming Instructions--Volume 1
NAPCO Security Group
Programming Instructions, Volume 1 Page 9
The above dialog presents 3 choices:
1. Click Yes to open the Error Check List dialog, listing the current errors in the Account;
2. Click No to continue with the download operation; be aware a qualified technician MUST be on site to unlock a
Fire keypad and enable the "ENABLE PROGRAMMING" selection in the keypad Function menu (ensuring the re-
quirement that all remote Fire-related downloads be "attended");
3. Click Cancel to abort the download operation.
"Error Check Required" Keypad Trouble
Generally, the "ERROR CHECK REQ'D" keypad trouble may appear in two ways. If errors are found in the Quickloader
account, and the account program (with errors) is downloaded to the panel, the keypad will warn of the errors by dis-
playing "ERROR CHECK REQ'D" in the keypad display. Another way the "ERROR CHECK REQ'D" keypad trouble will
appear is when the keypad Function Menu selection "ENABLE PROGRAMMING" is selected. As described above,
"ENABLE PROGRAMMING" must be enabled to allow access to the Direct Address Program Mode and/or the Easy Menu
-Driven Program Mode in order to program the control panel using the keypad.
The only way to clear this "ERROR CHECK REQ'D" keypad trouble is by using Quickloader. There are several ways to
do this in Quickloader.
One way to remove this "ERROR CHECK REQ'D" keypad trouble is by immediately correcting all errors in the Quick-
loader account, then performing a full download (or Smart Download) to the panel without errors. When the down-
load process completes, the "ERROR CHECK REQ'D" keypad trouble will be cleared.
Another way to remove this "ERROR CHECK REQ'D" keypad trouble is to upload the panel programming into the
Quickloader account, select the Attempt to Clear ERROR CHECK REQ'D Trouble radio button (in the Panel Commu-
nications dialog shown below) and click OK. The Quickloader error check will automatically run, and if er-
rors are found, the operation will abort; if no errors are found, Quickloader will then attempt to check if the account
and panel program are identical (if a mismatch is found, the operation will be aborted). Note: See Fire Glossary en-
try "Disable Panel Error Check Required Mode" in WI1653.
ENABLE PROGRAMMING Keypad Function Menu Selection
The "ERROR CHECK REQ'D" warning will also appear if "ENABLE PROGRAMMING" (located in the keypad Function
menu) is selected. The selection "ENABLE PROGRAMMING" is primarily designed to allow access to keypad Direct Ad-
dress Programming (and/or the Easy Menu-Driven Program Mode), and is also generally designed to allow for "non-
local" downloading. Since these keypad programming modes allow changes to be made to the panel program out-
REMOTE DOWNLOADING RULES (CONT'D)

Table of Contents

Other manuals for NAPCO GEMINI GEMC-128

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NAPCO GEMINI GEMC-128 and is the answer not in the manual?

NAPCO GEMINI GEMC-128 Specifications

General IconGeneral
BrandNAPCO
ModelGEMINI GEMC-128
CategoryControl Panel
LanguageEnglish

Related product manuals