X Series User Manual
Simple Pulse Generation
Refer to the following sections for more information about the X Series simple pulse generation
options:
•
Single Pulse Generation
•
Single Pulse Generation with Start Trigger
Single Pulse Generation
The counter can output a single pulse. The pulse appears on the Counter n Internal Output signal
of the counter.
You can specify a delay from when the counter is armed to the beginning of the pulse. The delay
is measured in terms of a number of active edges of the Source input.
You can specify a pulse width. The pulse width is also measured in terms of a number of active
edges of the Source input. You can also specify the active edge of the Source input (rising or
falling).
Figure 7-27 shows a generation of a pulse with a pulse delay of four and a pulse width of three
(using the rising edge of Source).
Figure 7-27. Single Pulse Generation
Single Pulse Generation with Start Trigger
The counter can output a single pulse in response to one pulse on a hardware Start Trigger signal.
The pulse appears on the Counter n Internal Output signal of the counter.
You can route the Start Trigger signal to the Gate input of the counter. You can specify a delay
from the Start Trigger to the beginning of the pulse. You can also specify the pulse width. The
delay and pulse width are measured in terms of a number of active edges of the Source input.
After the Start Trigger signal pulses once, the counter ignores the Gate input.
SOURCE
OUT
Counter Armed

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments 6368 and is the answer not in the manual?

National Instruments 6368 Specifications

General IconGeneral
BrandNational Instruments
Model6368
CategoryData Loggers
LanguageEnglish

Related product manuals