7.5 - Level2programming(adjustableparameters)
The adjustable parameters are factory set as shown in the Table 8 with: “ ” but can be modified at any time as shown in Table 9. Take care during modification
procedures, as there is a maximum time interval of 10 seconds between pressing one key and another; otherwise the system exits the procedure automatically
memorising the changes made up to that time.
TABLE8-Leveltwofunctions(adjustableparameters)
Entranceled Parameter Led(level) Value Description
L1 Pause Time L1 5 seconds Adjusts the pause time, namely the time
which lapses before automatic closure.
Is effective only if automatic closure is
enabled.
L2 15 seconds
L3 30 seconds
L4 45 seconds
L5 60 seconds
L6 80 seconds
L7 120 seconds
L8 180 seconds
L2 Step-by-
step
L1 Open - stop - close - stop Manages the sequence of controls associ-
ated to the Step-by-Step input or to the
1st radio command.
L2 Open - Stop - Close - Open
L3 Open - close - open - close
L4 Apartment block
L5 Apartment block 2 (more than 2” generates stop)
L6 Step-by-Step 2 (less than 2” causes partial opening)
L7 Hold-to-run
L8 “Semi-automatic” opening, “hold-to-run“ closing
L3 Motor
speed
L1 Very slow Sets the motor speed during normal travel.
L2 Slow
L3 Medium
L4 Fast
L5 Very fast
L6 Extremely Fast
L7 Opens “Fast”; closes “slow”
L8 Opens “Extremely Fast” Closes “Fast”
L4 Open Gate
Indicator
Output
L1 Open Gate Indicator Function Adjusts the function associated with S.C.A.
output. (whatever the associated function
may be, the output supplies a voltage of
24V –30 +50% with a maximum power of
4W when active).
L2 On if gate closed
L3 On if gate open
L4 Active with 2nd radio output
L5 Active with 3rd radio output
L6 Active with 4th radio output
L7 Maintenance indicator
L8 Electric lock
L5 Motor
Force
L1 Super light gate The force control system also measures
the ambient temperature, automatically
increasing the force in the event of particu-
larly low temperatures.
L2 “Very light” gate
L3 “Light” gate
L4 “Average” gate
L5 “Average heavy” gate
L6 “Heavy”gate
L7 “Very heavy” gate
L8 “Super heavy” gate
L6 Partial
open
L1 0,5 mt Adjusts the measurement of the partial
opening. Partial opening can be controlled
with the 2nd radio command or with
“CLOSE”, if the “Close” function is present,
this becomes “Open partially”.
L2 1 mt
L3 1,5 mt
L4 2 mt
L5 2,5 mt
L6 3 mt
L7 3,4 mt
L8 4 mt
L7 Mainte-
nance
warning
L1 Automatic (depending on the severity of the manoeuvre) Controls the number of manoeuvres after
whichtheautomationmaintenancenoti-
cation signal is sent (see paragraph 8.2.3
Maintenancenotication).
L2 1000
L3 2000
L4 4000
L5 7000
L6 10000
L7 15000
L8 20000