Installation | 10
Typical Humidifier Installation
Figure 4: Typical Humidifier Installation
36 in. (90 cm)
min. right
clearance
36 in. (90 cm)
min. front
clearance
24 in.
(60 cm)
min.
3 in. (7.5 cm) Screws
1- 24 VAC
2- On/Off Loop
3- Ctrl Ground
4- Control Signal
5- Limit Signal
6- 5 VDC
7- Ground
8- Blower Pack
9- Blower Pack
On/Off
Controls
Modulation
Controls
E
X
T
E
R
N
A
L
N
H
T
C
/
P
C
L1
L2
L3
Ground
Dedicated
Circuit
Breaker or
Disconnect
NHTC/PC
EXTERNAL
Cold potable water
350-670 microsiemens
30-80 psig
Air Gap
½ in NPT
2 in.
(5 cm)
min.
1ft (30 cm)
1 ft (30 cm)
min.
Mounting
Pg 12
Steam
Distribution
Pg 14
Controls
Pg 20
Plumbing
Pg 13
Electrical
Pg 19