Use of the Controls Programming Keypad
2.3.4 Drill
Use the DRILL key to manually activate all silenceable outputs and Notification Appliance Circuits.
To prevent accidental activation, you must press the
DRILL key for 2 seconds. When pressed, the
control panel does the following:
• Turns on all silenceable NACs
• Turns off the SIGNALS SILENCED LED
• Sends a Manual Evacuate message to the History buffer and installed printers, CRT-2
terminals, and FDU-80 annunciators
2.3.5 Lamp Test
Use the LAMP TEST key to test the control panel LEDs and the panel sounder. When pressed and
held, the control panel does the following:
• Lights all control panel LEDs
• Turns on the panel sounder
• Lights all segments of the LCD display. When the LAMP TEST key is held for longer than five
seconds, the LCD will display the Software Revisions.
2.4 Programming Keypad
The programming keypad includes:
• Function keys: DETECTOR, MODULE, OUTPUT, BATTERY LEVELS, NEXT SELECTION, PREVIOUS
SELECTION, RECALL LAST ENTRY, and INCREMENT NUMBER
• ENTER key
• Cursor movement keys: ESC/LEFT ARROW key, UP key, RIGHT key, DOWN key
• Alphabetic and numeric keys, with LOWER CASE selection key
Shown below is the Programming Keypad, with descriptions for the keys.
NOTE: If Local Control is set to “0” (NO) or “2” (Partial Control), the FACP will not respond to
DRILL.