NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 29
Active Trouble Monitor Mode of Operation Operation of the Control Panel
3.10.2 How the Control Panel Indicates an Active Fire Control
Activation of a FIRE CONTROL point causes the control panel to do the following:
Initiate the monitor module Control-by-Event
Send a message to the LCD display, History buffer and installed printers, FDU-80
annunciators, and CRT-2s
Display an ACTIVE status banner and FIRE CONTROL Type Code on the LCD display, along with
information specific to the device
Figure 3.13 Sample Fire Control Point Display
3.10.3 How the Control Panel Indicates an Active Non-Fire Point
Non-Fire point operation does not affect control panel operation, nor does it display a message at
the panel LCD. Activation of a Non-Fire point activates CBE—but does not cause any indication
on the control panel. For example, you can program a Non-Fire point to turn lights in a zone to a
lower setting when activated. In this case, when the point activates the control panel activates the
point’s CBE to turn the lights down without any audio or visual indication on the control panel.
3.11 Active Trouble Monitor Mode of Operation
3.11.1 How the Control Panel Indicates an Active Trouble Monitor
Trouble Monitor Points are monitor modules programmed with the following Type Codes:
These types of monitor modules operate like monitored system functions that can produce
troubles—but with the following differences:
The LCD display status banner displays ACTIVE as shown:
Figure 4 Sample Trouble Monitor Point Message
The monitor module is non-latching: the module will return to normal when the trouble
condition no longer exists.
The monitor modules activate Control-by-Event
Status banner
Type Code
Zone affected by the Fire Control
ACTIVE FIRE CONTROL INTENSIVE CARE UNIT
EASTERN WING Z055 08:59a 011511 1M044
Type Code
Latching
(Y/N)
Device Function Point Function
EQUIP MONITR N Used for recording access to monitored equipment Activates CBE
POWER MONITR N Used to monitor remote power supplies or other
external equipment
Indicates trouble
TROUBLE MON N Used to monitor remote power supplies or other
external equipment
Indicates trouble
Table 3.6 Trouble Monitor Type Codes
Status banner
Type Code
TROUBL TROUBLE_MON INTENSIVE CARE UNIT
EASTERN WING 09:38A 011511 1M044
Custom descriptor for
this device location
Device address
Time and date of trouble
Extended 12 character
custom label

Table of Contents

Other manuals for Notifier NFS-320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-320 and is the answer not in the manual?

Notifier NFS-320 Specifications

General IconGeneral
BrandNotifier
ModelNFS-320
CategoryControl Panel
LanguageEnglish

Related product manuals