NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 17
Fire Alarm Mode of Operation Operation of the Control Panel
In Normal mode, the control panel does the following functions at regular intervals:
Polls all SLC devices and the four NACs to check for valid replies, alarms, troubles, circuit
integrity, supervisory signals, etc.
Checks power supply troubles and batteries at 10-second intervals
Sends a supervisory query on the optional FDU-80 and verifies proper response
Refreshes the LCD display and the optional FDU-80 display and updates time
Scans for any keypad or Control Key entries
Performs a detector automatic test operation
Tests system memory
Monitors for microcontroller failure
3.3 Fire Alarm Mode of Operation
3.3.1 How the Control Panel Indicates a Fire Alarm
When an initiating device (detector or monitor module) activates, the control panel does the
following:
Produces a steady audible tone
Activates the System Alarm relay (TB4)
Flashes the FIRE ALARM LED
Displays a Type Code that indicates the type of device that activated the fire alarm
•Displays ALARM in the status banner on the LCD display, along with information specific to
the device, as shown below:
Figure 3.2 Sample Fire Alarm Display
Sends an Alarm message to the LCD display, History buffer and installed printers, FDU-80
annunciators, and CRT-2s.
Latches the control panel in alarm. (You can not return the control panel to normal operation
until you correct the alarm condition and reset the control panel)
Initiates any Control-By-Event actions
Starts timers (such as Silence Inhibit, Auto Silence)
Activates the general alarm zone (Z00)
3.3.2 How to Respond to a Fire Alarm
If the control panel indicates a fire alarm, you can do the following:
To silence only the panel sounder:
Press the ACKNOWLEDGE/SCROLL DISPLAY key. The local sounder will silence and the FIRE
ALARM LED will change from flashing to steady.
The control panel will send an acknowledge message to the LCD display, history buffer, and
installed printers, FDU-80 annunciators, and CRT-2s.
Status banner
Type Code of initiating device
Custom descriptor for
this device location
Device address
Time and date of trouble
Extended 12 character
custom label
ALARM: PULL STATION INTENSIVE CARE UNIT
EASTERN WING Z004 03:10P 011511 2M147
Zone

Table of Contents

Other manuals for Notifier NFS-320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-320 and is the answer not in the manual?

Notifier NFS-320 Specifications

General IconGeneral
BrandNotifier
ModelNFS-320
CategoryControl Panel
LanguageEnglish

Related product manuals