28 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Operation of the Control Panel Disabled Points Mode of Operation
3.9 Disabled Points Mode of Operation
The control panel indicates disabled points by displaying a screen for each disabled detector,
monitor module, and control/relay module. Disabled points do not cause an alarm or any
Control-by-Event activity. If more than one point is disabled, the control panel automatically
displays by priority, mimicking the alarms.
When one or more points are disabled, the control panel does the following:
Holds all disabled output points in the off-state
Flashes the SYSTEM TROUBLE LED
•Lights the POINT DISABLED LED
Sends a Disabled Point message to the LCD display, History buffer and installed printers,
FDU-80 annunciators, and CRT-2s
Displays a message for each disabled point
Figure 3.12 Sample Disabled Point Message
3.10 Non-Alarm Mode of Operation
3.10.1 Purpose of Non-Alarm Points
Non-Alarm points are addressable monitor modules programmed with one of the Non-Alarm Type
Codes listed in
Table 3.5. Non-Alarm points, except Non-Fire, operate like monitored system
functions that can produce troubles—but with the differences shown in the following sections.
!
CAUTION:
Disabling a zone disables all input and output devices associated with the zone if the zone is
in first zone “primary” mapped location.
Disable message
Type Code of the disabled device
Address of the
disabled device
DISABL TAMPER INTENSIVE CARE UNIT
EASTERN WING 03:20P 011511 1M159
Custom descriptor for
this device location
Time and date of trouble
Extended 12 character
custom label
Monitor Modules
Type Code
Latching
(Y/N)
Purpose What it does
ACCESS MONTR N Used for monitoring building access Activates CBE
ACK SWITCH N Performs Acknowledge function Silences panel sounder, gives an
Acknowledge message on the panel LCD
DRILL SWITCH N Performs Drill function Activates silenceable outputs
FIRE CONTROL N Used for air handler shutdown, intended to override
normal operating automatic functions
Activates CBE, does NOT light an
indicator at the control panel
NON-FIRE N Used for energy management or other non-fire
situations. Does not affect operation of the control panel
Activates CBE, does NOT light an
indicator at the control panel
PAS INHIBIT N Inhibits Positive Alarm Sequence Inhibits Positive Alarm Sequence
RESET SWITCH N Performs Reset function Resets control panel
SIL SWITCH N Performs Signal Silence function Turns off all activated silenceable outputs
ABORT SWITCH N Indicates Active at the panel Aborts activation of a releasing zone
Table 3.5 Non-Alarm Type Codes

Table of Contents

Other manuals for Notifier NFS-320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-320 and is the answer not in the manual?

Notifier NFS-320 Specifications

General IconGeneral
BrandNotifier
ModelNFS-320
CategoryControl Panel
LanguageEnglish

Related product manuals