NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 19
Fire Alarm Mode of Operation Operation of the Control Panel
SMOKE(PHOTO) Y Indicates activation of a photo smoke detector Lights FIRE ALARM LED and activates CBE
RF_PHOTO Y Indicates activation of a wireless photoelectric smoke
detector
Lights FIRE ALARM LED and activates CBE
SMOKE(DUCTL) Y Indicates activation of a duct laser detector Lights FIRE ALARM LED and activates CBE
SMOKE(DUCTP) Y Indicates activation of a duct photo smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(HARSH)* Y Indicates activation of a HARSH smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(LASER) Y Indicates activation of a laser smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(BEAM) Y Indicates activation of a beam smoke detector Lights FIRE ALARM LED and activates CBE
SMOKE(DUCTL) Y Indicates activation of a duct laser smoke detector Lights FIRE ALARM LED and activates CBE
AIR REF Y Indicates activation of a laser air reference detector. Lights FIRE ALARM LED and activates CBE
HEAT Y Indicates activation of a 190
o
F intelligent thermal detector Lights FIRE ALARM LED and activates CBE
HEAT+ Y Indicates activation of a 190
o
F adjustable threshold
intelligent thermal detector
Lights FIRE ALARM LED and activates CBE
HEAT(ANALOG) Y 135
o
F intelligent thermal sensor Lights FIRE ALARM LED and activates CBE
HEAT (ROR) Y 15
o
F per minute rate-of-rise detector Lights FIRE ALARM LED and activates CBE
SMOKE ACCLIM Y Indicates activation of detector without freeze warning Lights FIRE ALARM LED and activates CBE
SMOKE (ACCL+) Y Indicates activation of a detector with freeze warning Lights FIRE ALARM LED and activates CBE
SMOKE MULTI* Y Multi sensor smoke detector Lights FIRE ALARM LED and activates CBE
PHOTO/CO* Y Indicates activation of the Photo, Heat, or CO element of
a detector
Lights FIRE ALARM LED for photo and heat,
no LED will light for a CO alarm. Photo and
heat will activate CBE, CO alarm activates
special function zone FC and sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
PHOTO/CO
(P SUP)*
Y Indicates activation of the Photo, Heat or CO element of
a detector.
Lights FIRE ALARM LED for heat, no LED will
light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools)
PHOTO/CO
(C SUP)*
Y Indicates activation of the Photo, Heat or CO element of
a detector.
Lights FIRE ALARM LED for heat and photo
alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE zone
only (sixth CBE zone programmable via
VeriFire Tools)
*FlashScan mode only
Type Code
Latching
(Y/N)
Purpose What it does
Table 3.1 Fire Alarm Type Codes (2 of 2)