185
Wiring Section 5-4
CJ1W-DA041
CJ1W-DA08V (Voltage Output)
and CJ1W-DA08C (Current Output)
1. The analog output numbers that can be used are set in the Data Memory
(DM).
2. The output signal ranges for individual outputs are set in the Data Memory
(DM). They can be set in units of output numbers.
3. The N.C. terminals are not connected to internal circuitry.
4. We recommend the following external power supplies.
!Caution Use a separate power supply from the one used for Basic I/O Units. Faulty
Unit operation may be caused by noise if power is supplied from the same
source.
Voltage output 2 (+)
Output 2 (–)
Current output 2 (+)
Voltage output 4 (+)
Output 4 (–)
Current output 4 (+)
N.C.
N.C.
0 V
Voltage output 1 (+)
Output 1 (–)
Current output 1 (+)
Voltage output 3 (+)
Output 3 (–)
Current output 3 (+)
N.C.
N.C.
24 V
B1
B2
B3
B4
B5
B6
B7
B8
B9
A1
A2
A3
A4
A5
A6
A7
A8
A9
Maker Model number Specifications
OMRON S82K-05024 100 VAC, 50 W
S82K-10024 100 VAC, 100 W
S82J-5524 100 VAC, 50 W
S82J-5024 100 VAC, 100 W
B1
B2
B3
B4
B5
B6
B7
B8
B9
Output 2 (+)
Output 2 (−)
Output 4 (+)
Output 4 (−)
Output 6 (+)
Output 6 (−)
Output 8 (+)
Output 8 (−)
0 V
A1
A2
A3
A4
A5
A6
A7
A8
A9
Output 1 (+)
Output 1 (−)
Output 3 (+)
Output 3 (−)
Output 5 (+)
Output 5 (−)
Output 7 (+)
Output 7 (−)
24 V