6 - 7
6 Programless Communications
E5@C Digital Temperature Controllers Communications Manual (H175)
6-2 E5C Setup
6
6-2-1 Protocol Setting
6-2 E5C Setup
The parameters that are used for programless communications are shown with a gray background in
the following diagram. These parameters will be displayed if you set the Protocol Setting parameter to
fins, mcp4, or fxp4. (Some of the parameters are always displayed.) The parameters in the commu-
nications setting level are described first, followed by those in the adjustment level.
* These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
Set the Protocol Setting parameter to fins to connect to an OMRON PLC, mcp4 to connect to a Mit-
subishi Q-series or L-series PLC, fxp4 to connect to a Mitsubishi FX-series or Keyence KV-series
PLC, and cmp to use component communications. Refer to 6-1-5 Connectable PLCs for lists of the
PLCs that can be connected.
Refer to 7-1 Component Communications for information on component communications.
Communications Setting Level
Display condition: None
* Selection is possible only for E5@C version 2.1 or later.
6-2-1 Protocol Setting
Parameter name Displayed characters Setting range Default
Protocol Setting psel cwf: CompoWay/F
mod: ModbusRTU
cmp: Component communications
fins: Host Link (FINS)
mcp4: MC protocol (format 4)
fxp4: Dedicated protocol (format 4)*
cwf
Initial Setting Level
Operation Level
M
M
M
M
M
Protocol Setting
*
Communications
Unit No.
*
Communications
Baud Rate
*
Send Data Wait
Time
*
Highest
Communications
Unit No.
Area
Communications Setting Level
Power ON
M
M
M
M
M
First Address Upper
Word
First Address Lower
Word
Receive Data Wait
Time
Communications
Node Number
Upload Setting 1
M
M
M
M
Upload Setting 2
Download Setting 1
Download Setting 2
Copy
M
M
M
M
Adjustment Level
Display
AT Execute/Cancel
Communications
Writing
*
Work Bit 8 OFF Delay
Adjustment Level
M
M
Communications
Monitor
Press
O
Key for
less than 1 s.
Press
O
Key for
at least 3 s.
Press
O
Key for
at least 1 s.
Press
O
Key for
less than 1 s.
25
0
psel
fins
u-no
0
bps
57.6
sdwt
20
maxu
0
adrh
0
adrl
0
rwat
1000
unit
0
area
0
up 2
2
dn 1
31
dn 2
61
copy
off
up 1
1
l.adj
1234
at
off
cmwt
on
plcm
0
w8of
0
in-t
5