6 - 75
6 Programless Communications
E5@C Digital Temperature Controllers Communications Manual (H175)
6-10 Connecting to MELSEC iQ-R-series PLCs
6
6-10-3 PLC Setup
Set up communications on the RJ71C24 to enable communicating with the E5CC Controllers.
PLC operation will stop and the PLC will be reset during the setup procedure. Make sure that this will
not create any problems in the controlled system.
Connecting to the PLC
(1) Connect the computer to the CPU Module with a USB cable and then start GX
Works3.
(2) Select Online Read from PLC from the menu bar.
(3) The following dialog box will be displayed. Confirm that RCPU is selected and then
click the OK Button.
(4) The following dialog box will be displayed.
Click the OK Button to close the dialog box.
6-10-3 PLC Setup