2 - 15
2 CompoWay/F Communications Procedures
E5@C Digital Temperature Controllers Communications Manual (H175)
2-3 Detailed Description of the Services
2
2-3-7 Echoback Test
(3) Response Code
Normal Completion
Error Occurred
This service performs an echoback test.
Service Request PDU
Service Response PDU
(1) Test Data
Set between 0 and 200 bytes of user-defined test data.
Set a value for the test data within the ranges shown below according to the communications data
length.
(2) Response Code
Normal Completion
Error Occurred
Response code Name Description
0000 Normal completion No errors were found.
Response code Error name Description
1001 Command too long The command is too long.
2203 Operation error Non-volatile memory error
2-3-7 Echoback Test
Communications
data length
Test Data
8 bits ASCII data: H'20 to H'7E or H'A1 to H'FE
7 bits ASCII data: H'20 to H'7E
Response code Name Description
0000 Normal completion No errors were found.
Response code Error name Description
1001 Command too long The command is too long.
2203 Operation error Non-volatile memory error
MRC SRC
0801
22 0 to 200
Test data
MRC SRC
Response
code
0801
22
0 to 200
Test data
4

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
BrandOmron
ModelE5EC
CategoryTemperature Controller
LanguageEnglish

Related product manuals