6 - 83
6 Programless Communications
E5@C Digital Temperature Controllers Communications Manual (H175)
6-10 Connecting to MELSEC iQ-R-series PLCs
6
6-10-5 Checking Operation
(3) To make the value easier to check, change the values that are displayed to decimal
values.
Select View Display format Detailed Setting.
Set the display format settings shown in the following dialog box.
Set the Display Unit Format to Word Multi-point, set the Bit Order to 0-F, set the Word
Device Word Multi-point Format to 10 Points, and then click the OK Button.
The display will appear as shown below after the display format is changed.
The area where monitor values are checked is called the upload area.
D0 to D14 is the upload area for the No. 0 Controller (E5CC), D30 to D44 is the upload area
for the No. 1 Controller, and D60 to D74 is the upload area for the No. 2 Controller.
No.0
No.1
No.2