Parameter Details
12
12.2 b: APPLICATION
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 515
12.2 b: APPLICATION
The parameter group b: APPLICATION sets the following functions.
Frequency reference source/Run command source
Stopping method settings
DC Injection Braking
Speed Search
Timer Function
PID control
Dwell function
Droop control
Energy Savings Control
Zero Servo Control
b1: OPERATION MODE SELECT
b1 parameters set the operation mode for the drive.
b1-01 Freq. Ref. Sel. 1
No.
(Hex.)
Name Description
Default
(Range)
b1-01
(0180)
Freq. Ref. Sel. 1
Sets the input method for the frequency reference.
1
(0 - 4)
Note:
Push on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Min Output Frequency] value,
on the keypad will flash. Check the setting for the frequency reference input and enter a value more than or equal to the E1-09
value.
0 : Keypad
Use the keypad to enter the frequency reference.
Use and on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals AI1, AI2, and AI3 to input an analog frequency reference with a voltage or current input
signal.
Voltage Input
Refer to Table 12.3 to use a voltage signal input to one of the MFAI terminals.
Table 12.3 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
AI1 0 - 10 V H3-01 = 0 H3-02 = 0
[Frequency Reference]
H3-03 H3-04 Set DIP switch S1-1 to V for
voltage input.
-10 - 10 V H3-01 = 1
AI2 0 - 10 V H3-09 = 0 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1-2 to V for
voltage input.
-10 - 10 V H3-09 = 1
AI3 0 - 10 V H3-05 = 0 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S1-3 to V for
voltage input.
Set DIP switch S4 to AI for
analog input.
-10 - 10 V H3-05 = 1

Table of Contents

Other manuals for Omron Q2A-A4005-AAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A-A4005-AAA and is the answer not in the manual?

Omron Q2A-A4005-AAA Specifications

General IconGeneral
BrandOmron
ModelQ2A-A4005-AAA
CategoryController
LanguageEnglish

Related product manuals