EasyManuals Logo
Home>Omron>Control Unit>SYSMAC C200H-NC112

Omron SYSMAC C200H-NC112 User Manual

Omron SYSMAC C200H-NC112
185 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
20
Deviation counter
reset output
ORIGIN SEARCH
Origin proximity signal
Z-phase signal
Pulse output
Driver completed input
Busy flag
Approx. 30 ms
Time
In this example, the mode switch is set to 3 and the DIP switch pins are set
as follows:
1 OFF CW/CCW output
2 ON Origin search direction: CCW
3 ON Origin proximity present
4 ON Origin proximity signal from NO input (rising edge)
5 ON Origin signal from NO input (rising edge)
6 Refer to
Section 4–10 External Interrupt Commands
.
7
8 ON Origin proximity reverse present (rising, falling edge)
Origin search is started after the origin proximity signal has risen and fallen,
and the origin adjustment signal is output to the servomotor driver after de-
celeration is completed. The positioning completed signal is then input from
the servomotor driver and origin search ends. The servomotor driver stops
automatically with the first Z-phase input after it has received the origin ad-
justment signal.
Example 4:
Settings in Mode 3
Switch Settings Section 2–1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200H-NC112 and is the answer not in the manual?

Omron SYSMAC C200H-NC112 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200H-NC112
CategoryControl Unit
LanguageEnglish

Related product manuals