26
Operating using external signals
1. Guidance
Setting the operation data
Rotation speed display
AC power supply
MEXE02
Install and wire the
motor and driver.
Set the operation data.
Select the operation
data number.
Operate the motor.
External control equipment
Operation/standstill
Selection of operation data
Motor
Setting the operation data
Function extension
⇒USER MANUAL
2. Operation data
Up to 16 operation data can be set. (Operation data Nos. 0 to 15)
To set the data with the analog setting, the "Speed, torque limiting command selection" parameter is required to change.
Setting method
Item
Data setting
Digital setting Analog setting
Operation
panel
MEXE02
External
potentiometer
External DC
voltage
Setting range
Factory
setting
0 to 10 VDC
1 mA or more
External
Rotation speed 50 to 4000 [r/min] 50
● ● ● ●
Torque limiting
value
0 to 300 [%] 300
● ● ● ●
Acceleration time
Deceleration time
0.0 to 15.0 [s] 0.5
● ●
− −
Selection method
Select a desired operation data number by switching the ON-OFF status of the M0 and M1 inputs.
If the M0 and M1 inputs are not connected, the motor rotates at the rotation speed set in the operation data No.0.
Operation data No. M1 input M0 input Setting method
ON
OFF
ON
OFF
ON
OFF
No.0 No.1 No.2 No.3
input
input
Operation inpt
: FWD, REV input
0 OFF OFF
Digital setting
*
1 OFF ON
2 ON OFF
3 ON ON
*
The setting method can be changed to the analog setting.
If the M2 input and M3 input are assigned to the input terminals,
the operation data can be extended up to 16 data.
Operation/stop
⇒
p.30