Operating using external signals
27
3. Setting of rotation speed
The rotation speed can be set with the digital setting at the time of shipment. To set the data with the analog setting, the "Speed,
torque limiting command selection" parameter is required to change. Each setting procedure is shown below.
[Setting range: 50 to 4000 r/min] (Factory setting: 50 r/min)
Setting method
Digital setting Analog setting
Operation panel
MEXE02
External
potentiometer
External DC
voltage
0 to 10 VDC
1 mA or more
External
p.27
⇒
USER MANUAL p.28
Procedure to set the rotation speed with the operation panel
Example
: Set the rotation speed of the operation data No.0 to 1000 r/min.
1
Turn on the AC power
supply
Set (store) the data
Change to 1000 r/mim
2
3
Press twice
Press
4
5
6
Turn
Press
Data No.0
Data number
selection screen
Press
Rotation speed
Operation data selection screen
in the data number
Press
Setting screen of rotation
speed
50 r/min (factory setting)
Turn the operation input
signal ON
FWD : ON
Driver
CN5
2
3
9
FWD
REV
IN-COM1
The motor rotates.
If the input signal having been
turned ON is turned OFF, the
motor will stop.
REV : ON
Rotation speed: 0 r/min
[To return to the rotation speed display]
Press
Press Press
ve times
∗
The gures show the rotation direction of the
round shaft type motor with the factory setting.
Details about operation and stop
⇒
Refer to p.30 for details.