9
AC AND DC GROUNDING REQUIREMENTS
Connect only to a grounded, permanent wiring system. Ensure there is only one neutral-ground
connection in the system at any time. Some codes require this connection be made at the main
panel only.
Some generators have their own neutral ground connection. If a generator is used, its neutral-
ground connection will need to be disengaged for proper system operation.
For all installations, the negative battery conductor should be bonded to the grounding system at
one (and only one) point in the system.
OutBack products are not designed for use in a positive grounded system. Please contact OutBack
Technical Support for further information.
The equipment ground on each is marked with this symbol:
Box lug for grounding the FX chassis