16.4.18 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
Air short circuit at indoor unit
Clogged indoor unit air filter
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty indoor unit fan motor
Refrigerant shortage (refrigerant leakage)
Clogged expansion valve or strainer
Faulty indoor pipe temperature sensor
Faulty indoor unit PCB
Troubleshooting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-E7NKEW and is the answer not in the manual?

Panasonic CS-E7NKEW Specifications

General IconGeneral
Indoor unit typeWall-mountable
Indoor units quantity1
Indoor unit dimensions (WxDxH)870 x 214 x 290 mm
TimerYes
Built-in displayNo
Cooling capacity (max)- BTU/h
Air conditioner functionscooling, heating
Cooling capacity in watts (max)2050 W
Heating capacity in watts (max)2800 W
Cooling energy efficiency (EER, W/W)4.36
Heating energy efficiency (COP, W/W)4.41
Outdoor units quantity0
Noise level (low speed)20 dB
Noise level (high speed)37 dB
Noise level (medium speed)24 dB
Power requirementsAC 230 V

Related product manuals