13. Operation Control (For Multi Split Connection)
During multi split connection, indoor unit’s operation controls are same with single split connection unless specified in
this chapter.
13.1 Cooling operation
13.1.1 Thermostat control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting
temperature < -2.0°C.
Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting
temperature > Capability supply OFF point.
13.2 Soft Dry Operation
13.2.1 Thermostat control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature Internal setting
temperature < -3.0°C.
Capability resume to indoor unit after waiting for 3 minutes, if the Intake Air temperature Internal setting
temperature > Capability supply OFF point.
13.3 Heating Operation
13.3.1 Thermostat control
Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature Internal setting
temperature > +1.0°C.
During this condition, the indoor fan is stopped if compressor is ON.
Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air Temperature Internal
setting temperature < Capability supply OFF point.
13.3.2 Temperature Sampling Control
Temperature sampling is controlled by outdoor unit where room temperature for all power supply ON indoor unit
could be obtained.
When capability supply to the indoor unit is OFF and the compressor is ON, the indoor fan motor is stopped.
During this condition, 15 seconds after sampling signal from outdoor unit is received, the indoor fan start
operation at low fan speed.
However, within first 4 minutes of capability stopped supply to the indoor unit, even sampling signal is received,
the sampling control is cancelled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-E7NKEW and is the answer not in the manual?

Panasonic CS-E7NKEW Specifications

General IconGeneral
Indoor unit typeWall-mountable
Indoor units quantity1
Indoor unit dimensions (WxDxH)870 x 214 x 290 mm
TimerYes
Built-in displayNo
Cooling capacity (max)- BTU/h
Air conditioner functionscooling, heating
Cooling capacity in watts (max)2050 W
Heating capacity in watts (max)2800 W
Cooling energy efficiency (EER, W/W)4.36
Heating energy efficiency (COP, W/W)4.41
Outdoor units quantity0
Noise level (low speed)20 dB
Noise level (high speed)37 dB
Noise level (medium speed)24 dB
Power requirementsAC 230 V

Related product manuals