TWP/TWB200 – TWP/TWB9000
32
Advance Settings
Control Air Pressure
Regeneration will pause wen the inlet pressure drops 10 psi (68 kPa) below the settings.
Regeneration will resume when the pressure rises above the setting.
Purge Temperature
Maintains purge temperature is this level during heating.
Over-temp Temperature
Shuts down dryer if purge temperature sensor rises above this setting.
This is independent of external over-temp alarm.
Heat Exhaust Limit / Enable
Halts heating 5 minutes after exhaust temperature rises above setting.
Cool Exhaust Limit / Enable
Halts Cooling 5 minutes after exhaust temperature falls below setting.
Enable Shutdown Dryer on Bad Blow down
If this setting is enabled, the dryer will alarm and regeneration will shut down if the tower pressure is over 10 psi at
the end of the blow-down time.
If this setting is disabled, the dryer will wait indenitely until the tower pressure drops below 10psi before proceeding
to regeneration.