- 30 -
GB
S31 Room SetPoint PHASE1 -18°C Hard -40°C -60°C 100°C
S32 Core SetPoint PHASE1 -18°C Hard -18°C -60°C 100°C
S33 Time SetPoint PHASE1 -18°C Hard 80min 0min 900min
S34 Room SetPoint PHASE2 -18°C Hard -40°C -60°C 100°C
S35 Core SetPoint PHASE2 -18°C Hard -18°C -60°C 100°C
S36 Time SetPoint PHASE2 -18°C Hard 80min 0min 900min
S37 Room SetPoint PHASE3 -18°C Hard -40°C -60°C 100°C
S38 Core SetPoint PHASE3 -18°C Hard -18°C -60°C 100°C
S39 Time SetPoint PHASE3 -18°C Hard 80min 0min 900min
S40 Time SetPoint in to P99 -18°C 240min 0min 900min
SetPoint Description Default min MAX
fig. 11
fig. 12
fig. 13
fig. 14
fig. 15
• DISPLAY1 shows the year value
• DISPLAY2 shows the “yy” symbol
Press key and to change the year values (fig. 11)1)
Press key to confirm the inserted value. This is followed by a display of the
month (fig.12),
day (fig.13),
hour (fig.14),
minutes (fig.15).
4.9 Time, only with printer (optional)
After switching the machinery off from key , it is possible to change the Time by simultaneously pressing, for five
seconds, key and key
4.8 Printer (optional) Mod. no Mod. R _ _ 51S
If a printer is present, the following is printed for each blast chiller cycle:
Time, type of cycle and sampled temperature every P44 minutes.
To enable printer P41=1