11 Table of Anomaly Signals
In case of malfunctioning of the system, the controller switches off the
regulation output and displays the type of anomaly.
For example the controller will signals the breakage of any connected
thermocouple by displaying ( ashing) on display.
#
Cause What to do
E-01
Error in EEPROM cell
programming.
Call Assistance.
E-02
Cold junction sensor fault or
room temperature outside of
allowed limits.
Call Assistance.
E-04
Incorrect con guration data.
Possible loss of calibration
values.
Check if the con guration
parameters are correct.
E-05
Thermocouple open or
temperature outside of limits.
Check the connection with the
sensors and their integrity.
E-08
Missing calibration data. Call Assistance.