UB40.241
UB-Series
24V, 40A, DC-UPS
Jun. 2020 / Rev.0.1 DS-UB40.241-EN All values are typical figures specified at 24Vdc input voltage, 40A output current in
power supply mode at 25°C ambient, no charging and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13. CONNECTION TERMINALS
The terminals are IP20 finger safe constructed and suitable for field and factory wiring.
Input, output and battery
terminals
Signal terminals (except
battery-low pre-warning)
Battery-low pre-warning
terminals
Type
Screw terminals
Pluggable screw
terminals
Push-in termination
Solid wire
Max. 16mm
2
Max. 1.5mm
2
Max. 1.5mm
2
Stranded wire
Max. 10mm
2
Max. 1.5mm
2
Max. 1.5mm
2
American Wire Gauge
AWG 22-8
AWG 22-14
AWG 24-16
Max. wire diameter (including ferrules)
5.2mm
1.5mm
1.6mm
Wire stripping length
12mm / 0.5inch
6mm / 0.25inch
7mm / 0.28inch
Tightening torque
2.3Nm / 20lb.inch
0.4Nm / 3.5lb.inch
-
Screwdriver
Slotted 6.5mm, Philips No
2
Slotted 3mm
Slotted 3mm to open the
spring