UB40.241
UB-Series
24V, 40A, DC-UPS
Jun. 2020 / Rev.0.1 DS-UB40.241-EN All values are typical figures specified at 24Vdc input voltage, 40A output current in
power supply mode at 25°C ambient, no charging and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22.7. UZW24.100 CONNECTION AND WIRING KIT
The UZW24.100 is a wiring kit for batteries which are not supplied by PULS or larger sized batteries. It
includes the necessary cabling and a 60cm fastening strap for fixing to the battery. The battery wiring
is optimized for 26Ah batteries.
The wiring kit also includes a sensor board, which contains a temperature sensor and a center-tap
connection terminal. The use of the sensor board enables to monitor and charge the two batteries
individually and precisely. This extends the service life of the batteries and makes the use of matched
batteries unnecessary. The use of the sensor board is optional, and the DC-UPS will function without
the sensor board installed.
Temperature
Temperature
Center Tap
+
-
PT1000
Temp. Sensor
Fuse and
Connection
Board
UZW24.100 Wiring scheme
,
22.8. UZW24.101 CONNECTION AND WIRING KIT
The UZW24.101 is the same as the UZW24.100 but with a 1m fastening strap and without the cabling
for battery connection.
Temperature
Temperature
Center Tap
+
-
PT1000
Temp. Sensor
Fuse and
Connection
Board
UZW24.101 Wiring scheme