Parallel use for redundancy
Use two DC-UPSs with two individual power supplies, two battery modules and one decoupling module to build a redundant system.
Recommendations for building redundant systems:
a) Use separate input fuses for each power supply.
b) Set the power supply into “Parallel use” mode if available.
c) Use a redundancy module to decouple the two power sources.
d) Monitor the individual sources. Therefore, use the alarm contacts of the power supplies.
e) It is desirable to set the output voltages of all power supplies to the same value (± 100mV) or leave it at the factory setting.
Please note that the maximal allowed capacitive or inductive load do not double or multiply, when modules are connected in parallel.