Jun. 2020 / Rev.0.1 DS-UB40.241-EN All values are typical figures specified at 24Vdc input voltage, 40A output current in
power supply mode at 25°C ambient, no charging and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
Setting of battery size
selector
2x 12V batteries in series
Recommended battery sizes
Required min. battery
voltage for charging
Center-tap connected
Center-tap not connected
Below this voltage level, charging
does not start and the DC-UPS
reports “check wiring”
To avoid overloading of the power
supply, charging current is
automatically reduced when the input
current is larger than 40A
At battery temperatures above +50°C
or below -15°C
At battery voltages below 20V
At input voltages below 22.8V
Center-tap connected,
no temperature sensor connected
Center-tap not connected,
no temperature sensor connected
2x 13.1 to 14.2V (below +50°C), 2x 12.9 at 60°C
(13.6V applies for +20°C and changes with -18mV/°C)
Center-tap connected,
temperature sensor connected
26.2V to 28.4V (below +50°C), 25.8V (at +60°C)
(27.2V applies for +20°C and changes with -36mV/°C)
Center-tap not connected,
temperature sensor connected
Temperature range for
which the charging process is
enabled
Corresponds to the temperature
readings of the external temperature
sensor
Deep-discharge protection
At 0A, center-tap connected
At 40A, center-tap connected
At 0A, center-tap not connected
At 40A, center-tap not connected
Battery discharge current
In battery mode at no output current
Charging times:
The below listed charging time applies for a complete discharged battery until the DC-UPS indicated “Ready” with the green status LED.
In practice, the charging time can be much shorter, since the battery is usually not completely discharged.
For a 12Ah battery in 12Ah setting
For a 26Ah battery in 26Ah setting
For a 65Ah battery in 65Ah setting
For a 150Ah battery in 150Ah setting
An extensive longer charging time is most likely caused by a defective or outdated battery.