Page33
P605 Volume Units
This parameter determines the units that will be used in calculating volume
conversion. It is used in conjunction with P607 (maximum volume), please
note that there is no provision for the volume units descriptor to be shown
on the display.
The choices are:
Option Description
0 = No Units Volume will be totalised with no units
1 = Tons Volume will be totalised in Tons
2 = Tonnes Volume will be totalised in Tonnes
3 = Cubic metres Volume will be totalised in cubic metres
4 = Litres Volume will be totalised in litres
5 = UK Gallons Volume will be totalised in UK Gallons
6 = US Gallons Volume will be totalised in US Gallons
7 = Cubic feet Volume will be totalised in cubic feet
8 = Barrels Volume will be totalised in barrels
P606 Correction Factor
This parameter is used to enter a correction factor, when required, such as
the specific gravity of the material so that the volume calculated is relative
to the actual amount of material that can be contained between empty level
(P105) and 100% of span (P106). Default = 1
P607 Max Volume
This parameter displays the actual maximum volume that has been
calculated by the IMP+
IMP+IMP+
IMP+, i.e. P604 Calculated Volume x P606 Correction
Factor, and is a Read Only parameter. The volume displayed will be shown
in P605 Volume Units and is the total volume available between empty
level (P105) and 100% of span (P106).