MULTI TYPE
2, 3, 4 ROOMS TYPE
8. Airflow
Conversion factor:
•1 m
3
/h = 0.2778 l/s = 0.5886 CFM
•3.6 m
3
/h = 1 l/s
• 1.699 m
3
/h = 1 CFM
8-1. Compact cassette type
Model
Operation
mode
Fan speed
Airflow
m
3
/h
l/s CFM
RICH7AVFJ
Cooling
High 540 150 318
Med 490 136 288
Low 440 122 259
Quiet 390 108 230
Heating
High 540 150 318
Med 490 136 288
Low 440 122 259
Quiet 390 108 230
RICH9AVFJ
Cooling
High 540 150 318
Med 490 136 288
Low 440 122 259
Quiet 390 108 230
Heating
High 540 150 318
Med 490 136 288
Low 440 122 259
Quiet 390 108 230
RICH12AVFJ
Cooling
High 610 169 359
Med 530 147 312
Low 470 131 277
Quiet 410 114 241
Heating
High 610 169 359
Med 530 147 312
Low 470 131 277
Quiet 410 114 241
RICH18AVFJ
Cooling
High 750 208 441
Med 610 169 359
Low 520 144 306
Quiet 410 114 241
Heating
High 800 222 471
Med 710 197 418
Low 600 167 353
Quiet 450 125 265