Rockwell Automation Publication 440R-UM013F-EN-P - July 2021 79
Appendix A Specifications
Safety Outputs Specifications
Auxiliary Output Specification
Attribute 440R-S13R2 (CI) 440R-D22R2 (DI) 440R-D22S2 (DIS) 440R-EM4R2 (EM) 440R-EM4R2D (EMD) 440R-S12R2 (SI)
Wiring Terminal
13/14,
23/24, 33/34
13/14, 23/24
14, 24,
34, 44
13/14,
23/24,
33/34, 43/44
17/18,
27/28,
37/38, 47/48
13/14, 23/24
Output Type 3 N.O. 2 N.O. 4 PNP 4 N.O. 4 N.O. delayed 2 N.O.
Thermic Current I
th
1 x 6 A — 1 x 6 A
Fuses output (external) 6 A slow blow or 10 A quick blow — 6 A slow blow or 10 A quick blow
Switched Current, Min [mA] 10 — 10
Switched Voltage, Min [V] 10 — 10
Mechanical Life 10,000,000 cycles — 10,000,000 cycles
Rating
UL: C300
AC-15: 1.5 A / 250V AC
DC13: 2 A / 24V DC (0.1 Hz)
14, 24: 1.5 A each
34, 44: 0.5 A each
UL: B300
AC-15: 1.5 A / 250V AC
DC13: 2 A / 24V DC (0.1 Hz)
UL: C300
AC-15: 1.5 A/ 250V AC
DC13: 2 A/24V DC (0.1
Hz)
Capacitance —
14, 24: 1.6 µF each
34, 44: 9 µF each
—
Contact material AgNi AgNi + 0.2 µ Au — AgNi
Reaction Time
Safety Output
[ms]
L12
150
45 35
100 150 150Inputs 35 25
Mat Operation 40 30
Reaction Time
Single Wire
Safety Output
[ms]
L12 — 35 35
0150
—
Inputs 25 25 25 25
Mat Operation303030 30
Response
Time
Safety Output
[ms]
Inputs 35 35 25
35
35
Mat Operation 45 40 30 45
Response
Time
Single Wire
Safety Output
[ms]
Inputs 25 25 25
25
25
Mat Operation 35 30 30 35
Single-wire
Fault
45 45 45 45
Recovery Time [ms] 100 100 100 150 150 100
Attribute 440R-S13R2 (CI) 440R-D22R2 (DI) 440R-D22S2 (DIS) 440R-EM4R2 (EM) 440R-EM4R2D (EMD) 440R-S12R2 (SI)
Wiring Terminal — Y32 X32 Y32
Output Type 1 N.C. 1 PNP, 50 mA max