Using the Command Interface
105
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.18 Store_Extended_Total_Configuration
Purpose
With this call, the required total configuration of the AS interface is transferred to
the AS-i master and stored permanently in the EEPROM as the expected
configuration. This configures the DP/AS-i Link 20E.
The following data are transferred:
S The list of configured AS-i slaves specifying the AS-i slaves that can be
activated by the AS-i master in the protected mode.
S The list of configuration data specifying the ID codes and I/O configurations the
AS-i slaves must have.
S The list of AS-i slave parameters configured on the AS-i master and stored in
non-volatile memory. These parameters are transferred to the AS-i slaves when
the AS-i master starts up.
S The flags that determine the operating status of the AS-i master following start
up.
This call is not made in the protected mode.
For AS-i slaves that comply with the standard profile 7.4, the AS-i master manages
the parameter assignment itself. The parameter values for slaves complying with
standard profile 7.4 specified in the call are ignored by the AS-i master.
If you use CPUs from the SIMATIC S7 system as the PROFIBUS DP master, then
dependent on the configuration in STEP 7, these may send a complete AS-i slave
configuration to the DP/AS-i Link 20E during the DP startup. Use of the call
described here is then generally unnecessary.
Structure of the Job Data in the Send Buffer
Byte Meaning
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Command number: 3Ah
1 00h
2 LPS slave
0
LPS slave
1
LPS slave
2
LPS slave
3
LPS slave
4
LPS slave
5
LPS slave
6
LPS slave
7
3 LPS slave
8
LPS slave
9
LPS slave
10
LPS slave
11
LPS slave
12
LPS slave
13
LPS slave
14
LPS slave
15
4 LPS slave
16
LPS slave
17
LPS slave
18
LPS slave
19
LPS slave
20
LPS slave
21
LPS slave
22
LPS slave
23
5 LPS slave
24
LPS slave
25
LPS slave
26
LPS slave
27
LPS slave
28
LPS slave
29
LPS slave
30
LPS slave
31
6 reserved LPS slave
1B
LPS slave
2B
LPS slave
3B
LPS slave
4B
LPS slave
5B
LPS slave
6B
LPS slave
7B

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens DP/AS-Interface Link 20E and is the answer not in the manual?

Siemens DP/AS-Interface Link 20E Specifications

General IconGeneral
BrandSiemens
ModelDP/AS-Interface Link 20E
CategoryComputer Hardware
LanguageEnglish

Related product manuals