Using the Command Interface
86
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.5 Store_Actual_Parameters
Purpose
With this call, the configured parameters stored on the EEPROM are overwritten
with the current, permanently stored (actual) parameters; in other words, the
parameters of all the AS-i slaves are configured.
For AS-i slaves that comply with the AS-i slave standard profile 7.4, the AS-i
master manages the AS-i slave parameter assignment itself. The configured
parameters for these AS-i slaves always have the value F
H
.
Structure of the Job Data in the Send Buffer
Byte Meaning
0 Command number: 04
H