Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Engineering 2019-04-09
2.5 Equipment combinations
2.5.1 2-port / 3-port threaded valves with stroke actuator SAS..
Typical applications:
· Heating plants
· District heating plants
· Ventilation and air conditioning plants
Actuators
Stroke
Positioning force
Data sheet
SAS..
5.5 mm
400 N
N4581
PN 16 VVG44..
PN 16
VXG44.. SAS..
Medium 1…120 °C Medium 1…120 °C DN G k
∆p
∆p
Data sheet N4364 Data sheet N4464 [Inch] [m
3
/h] [kPa] [kPa]
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 0.25 / 0.4 / 0.63 400 1600
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 1 / 1.6 400 725
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 2.5 / 4 400 400
VVG44.20-6.3 VXG44.20-6.3 20 G 1 1/4 B 6.3 400 750
VVG44.25-10 VXG44.25-10 25 G 1 1/2 B 10 400 400
VVG44.32-16 VXG44.32-16 32 G 2 B 16 250 250
VVG44.40-25 VXG44.40-25 40 G 2 1/4 B 25 125 125
PN 25 VVG55..
2)
SAS..
Medium 1…130 °C DN G k
∆p
∆p
Data sheet N4379 [Inch] [m
3
/h] [kPa] [kPa]
VVG55.15-..
1)
15 G 3/4 B 0.25 / 0.4 / 0.63 1200 2500
VVG55.15-..
1)
15 G 3/4 B 1 / 1.6 / 2.5 1200 2000
VVG55.20-4 20 G 1 B 4 1000 1000
VVG55.25-6.3 25 G 1 1/4 B 6.3 800 800
1)
.. = insert k
vs
value
2)
.. = VVG55 to be replaced by VVG549 as of January 1, 2017
2.5.2 2-port / 3-port threaded valves with stroke actuator SAS..
and SAT..
Typical applications:
· District heating plants
Actuators
Stroke
Positioning force
Data sheet
SAS..
5.5 mm
400 N
N4581
SAT..
5.5 mm
300 N
N4584
PN 25 VVG549..
SAS..
1), 2)
SAT..
1)
Medium 2...130 °C DN G k
∆p
∆p
∆p
∆p
Data sheet Q4380 [Zoll] [m
3
/h] [kPa] [kPa] [kPa] [kPa]
VVG549.15-0.25
15 G 3/4 B
0,25
1200
2500
1200
2500VVG549.15-0.4 0,4
VVG549.15-0.63 0,63
VVG549.15-1 1
1500
1500VVG549.15-1.6 1,6
VVG549.15-2.5 2,5
VVG549.20-4K
3)
20 G 1 B 4
1600
1600
VVG549.25-6.3K
3)
25 G 1 1/4 B 6,3
1)
Briefly 150 °C (up to 150 °C max. 6 of 24 hours), with ALG..B fittings up to 100 °C
2)
SAS.. combined with VVG549: Change setting on the DIL switch to linear (factory setting = log).
SAS../MO: Change Modbus register 263 to 0 = linear ® only possible with Firmware release 2.0, not
with 0.27 and 1.0!
3)
Pressure compensated