Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Functions and control 2019-04-09
After calibration is completed, the actuator follows the external setpoint, the
warning is reset, the LED on the cover changes to continuous green and the cable
adapter blinks green (communication active).
Observe status indication (LED) during and after calibration (page 43).
4.3.4 Manual adjustment
The actuators internal stroke position measurement is inactive during manual
adjustment.
The position feedback changes to 0% once the manual adjuster is pressed and
remains on the value during manual adjustment. The actuator detects manual
action based on the deviation between the setpoint and the stroke position and
reports in register 769 with the warning “Mechanical error, device blocked, manual
intervention or calibration”. The LED on the actuator cover blinks green, the LED
on the cable adapter is red.
Upon return to automatic mode, the actuator synchronizes to stroke position 0%.
After the synchronization, the actuator follows the pending setpoint, the LED on the
cover changes to continuous green and, on the cable adapter, blinking green
(communication active). The warning in register 769 is reset.
Note

Table of Contents

Other manuals for Siemens MT SAS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MT SAS Series and is the answer not in the manual?

Siemens MT SAS Series Specifications

General IconGeneral
BrandSiemens
ModelMT SAS Series
CategoryController
LanguageEnglish

Related product manuals