39 / 60
Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Functions and control 2019-04-09
4.3.5 Parameters and function description
Reg. Name R/W Unit Scaling Range / listing
Process values
1 Setpoint RW % 0.01 0..100
2 Forced control RW -- -- 0 = Off / 1 = Open / 2 = Close
3 = Stop / 4 = Min / 5 = Max
3 Actual value
position
R % 0.01 0..100
256 Command RW -- 0 = Ready / 1 = Adaption / 2 = Self test
3 = Reinitialize / 4 = Remote reset
Parameters
259 Op mode RW -- -- 1 = POS
260 MinPosition RW % 0.01 0..100
261 MaxPosition RW % 0.01 0..100
262 Actuator runtime R s 1 30
263 Positioning signal
characteristic
between Y and U
RW -- -- 0 = Linear (e.g. SAX61../MO + V_G41)
1 = Logarithmic (e.g. SAS61../MO + V_G44)
264 Tolerance
blockade
monitoring
RW % 0.01 0..10
513 Backup mode RW -- -- 0 = Move to backup position
1 = Maintain last position / 2 = Disable
514 Backup position RW % 0.01 0..100
515 Backup timeout RW s 1 0..65535
516 Startup setpoint RW % 0.01 0..100
764 Modbus address RW -- -- 1..247 / 255 = “unassigned”
765 Baud rate RW -- -- 0 = auto / 1 = 9600 / 2 = 19200 3 = 38400
4 = 57600 / 5 = 76800 / 6 = 115200
766 Transmission
format
RW -- -- 0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2
767 Bus termination RW -- -- 0 = Off / 1 = On
768 Bus config.
command
RW -- -- 0 = Ready / 1 = Load / 2 = Reject
769 Status R
-- --
See Section, Register 769 “Status”