40 / 60
Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Functions and control 2019-04-09
Reg. Name R/W Value Example
Device information
1281 Factory Index R Two bytes, each
coding an ASCII char.
00 5A à 00 “Z”
Device is of Series “Z”
1282 Factory Date HWord R Two bytes, the lower
coding the Year (hex)
Read 1282 à 000F
Read 1283 à 0418
HWord LWord
-- YY MM DD
Hex 00 0F 04 18
Dec 00 15 04 24
à Device was manufactured
24 April, 2015
1283 Factory Date LWord R High byte: coding the
month (hex)
Low byte: coding the
day (hex)
1284 Factory SeqNo HWord R Hword + LWord =
HEX-representation
of Sequence number:
Read 1284 à 000A
Read 1285 à A206
AA206(hex) à 696838 (dec)
à Device has sequence
number 696838
1285 Factory SeqNo LWord R
1409 ASN [Char_16..15] R Each register: Two
bytes, each coding an
ASCII char.
ASN is coded
beginning with reg.
1409
Example:
0x47 44 = GD
0x42 31 = B1
0x38 31 = 81
0x2E 31 = .1
0x45 2F = E/
0x4D 4F= MO
à ASN is GDB181.1E/MO
1410
ASN [Char_14..13]
R
1411
ASN [Char_12..11]
R
1412
ASN [Char_10..9]
R
1413 ASN [Char_8..7] R
1414
ASN [Char_6..5]
R
1415 ASN [Char_4..3] R
Reserve
1416 ASN [Char_2..1] R
Status
Bit 00 1 = Reserved Bit 06 1 = Adaption conducted
Bit 01 1 = Backup mode active Bit 07 1 = Adaption running
Bit 02 1 = Reserved Bit 08 1 = Adaption error
Bit 03 1 = Reserved Bit 09 1 = Self test failed
Bit 04 1 = Mechanical error, device blocked,
manual intervention or calibration
Bit 10 1 = Self test successful
Bit 05 1 = Life cycle reached Bit 11 1 = Invalid configuration
Function codes
03 (0x03) Read Holding Registers
04 (0x04) Read Input Registers
06 (0x06) Write Single Register
16 (0x10)
Write Multiple Registers (Limitation: Max. 120 registers on one write access)
Function Reg. Description
Override
control
2 The actuator can be operated in override control for commissioning /
maintenance purposes or system-wide functions (e.g. night-cooling).
· Manual override: When the gear disengagement is used to freely adjust the
damper position, a mechanical jam will be detected if a mismatch between
setpoint and actual position persists for more than 10s.
· Remote override: The actuator enters this state when an override command
is sent over the bus.
· Available commands:
o
Open / Close (depends on opening direction)
Register 769 “Status”
Supported function
codes

Table of Contents

Other manuals for Siemens MT SAS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MT SAS Series and is the answer not in the manual?

Siemens MT SAS Series Specifications

General IconGeneral
BrandSiemens
ModelMT SAS Series
CategoryController
LanguageEnglish

Related product manuals