47 / 60
Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Smart Infrastructure Technical data 2019-04-09
SAS.. SAT..
Parallel operation SA..61.. ≤ 10 (depending on controler output)
Forced control Positioning signal Z SA..61.. R= 0…1000 Ω, G, G0
R = 0…1000 Ω Stroke proportional to R
Z connected to G Max. stroke 100 % Max. stroke 100 %
Z connected to G0 Min. stroke 0 % Min. stroke 0 %
Voltage Max. AC 24 V ± 20 % / Max. DC 24 V + 20 % / -15%
Current draw ≤ 0.1 mA
Position feedback U Voltage range SA..61.. DC 0...10 V
Load impedance > 10 kΩ res.
Load Max. 1 mA
Connecting cable Wire cross-sectional areas 0.75…1.5 mm
, AWG 20…16
Cable entries SA.. EU:
1 entry Æ 16.4 mm (for M16)
1 entry Æ 20.5 mm (for M20)
Thread length max. 9 mm
SA..U US:
2 entries Æ 21.5 mm for ½“ tube connection
SAS61../MO
Fixed connecting cable 0.9m
-
Number of wires
5 x 0.75 mm
2
Degree of protection Housing protection IP 54 as per EN 60529
Insulation class As per EN 60730
Actuators SA..31.. AC 230 V II
Actuators SA..61.. AC / DC 24 V III
Actuators SA..81.. AC / DC 24 V III
Environmental
conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5
Mounting location Indoors, outdoors
Temperature general -5…55 °C
Humidity (noncondensing) 5…95 % r. h.
Transport IEC 60721-3-2
Climatic conditions Class 2K3
Temperature -25…70 °C
Humidity <95 % r. h.
Storage IEC 60721-3-1
Temperature -15…55 °C
Humidity 5…95 % r. h.
Directives and
Standards
Product standard EN60730-x
Electromagnetic compatibility (Application) For residential, commercial and industrial environments
EU Conformity (CE) SAS..: CE1T4581xx
SAT..: CE1T4584xx
4)
RCM Conformity SAS..: CE1T4581en_C1
SAT..: CE1T4584en_C1
4)
UL, cUL AC / DC 24 V
UL 873 http://ul.com/database
EAC compliance
Eurasia compliance for all SA..-variants
Environmental
compatibility
The product environmental declaration CE1E4581
and A6V101083254
contains data on environmentally
compatible product design and assessments (RoHS compliance, materials composition, packaging,
environmental benefit, disposal).
Dimensions See Dimensions (page 53)
Weight Excl. packaging See Dimensions (page 53)
Accessories
Auxiliary switch ASC10.51 Switching capacity AC 24…230 V, 6 (2) A, floating
External supply line protection See section power supply
US installation, UL & cUL AC 24 V class 2, 5 A general purpose
Data sheet N4581 N4584
1)
Second value: Power consumption in neutral position
2)
AWG = American wire gauge
Wire cross-sectional areas and fuses have to be well-matching, which is the responsibility of the
planner / installer. Observe norm of protection measures - protection against overcurrent:
IEC 60364-4-43:2008 resp. german adoption HD 60364-4-43:2010.
3)
Outdoors always with weather shield ASK39.2, housing protection IP54 remains unchanged
SAS61../MO is not suitable for outdoor applications.
4)
The documents can be downloaded from http://siemens.com/bt/download
5)