5.3.1 Commissioning parameter via PCT Go
Selecting "Commissioning" in the menu, PCT Go can:
● Read and write thermostat parameters
● Set the application (e.g. 2-pipe)
● Change settings (e.g. setpoints)
● Set KNX addressing (device address) (RDG2..KN)
● Share commissioning data via standard communication tools, e.g., email
● Generate commissioning report
When set locally with the PCT Go app, the device can be reset using the system
tools and reconfigured as needed.
DIP switch settings take priority:
● PCT Go can be used to change the application (e.g. 2-pipe) if all DIP switches
are set to Off (default).
● PCT Go cannot change settings if an application is set via DIP switches.
Change settings while the device is powered and running:
● Application settings require a device reboot.
● Settings such as setpoint and HMI tuning take effect a few seconds later.
Change settings while the device is unpowered:
● Current thermostat settings can be read and written any time while unpowered
● The thermostat needs to be powered to store the new settings and ensure they
are correct.
● Each time the application is changed, the thermostat reloads the factory setting
for all control parameters, except KNX device and zone addresses.
● Access to thermostat settings can be password protected (P502). PCT Go
requires that the password be read and write-protected.
The thermostat is locked after 5 attempts for 5 minutes.
● Commissioning using PCT Go can be disabled via parameters to prevent
unexpected changes of the thermostat (P500).