24 / 44
Siemens Application Guide «Fire Mode» CM1A5192en_01
Building Technologies Application Examples 23.10.2007
4.6 Application Example 6
4.6.1 Description
• In normal operation the internal SED2 PID loop is working and managing the
pressure e.g. in a stairway. This application is equivalent to application 4 in the
Commissioning Guide CM1G5192 just enhanced with the ESM function.
• In case of fire the fire control panel signals this to the SED2, it is going in the
ESM mode and to a fixed frequency e.g. 40Hz.