Technical specifications
12.3 Shipping and storage conditions
CPU 1515SP PC2 (F/T/TF)
Operating Instructions, 09/2018, A5E42603425-AA
73
12.3
Shipping and storage conditions
Introduction
The CPU 1515SP PC2 exceeds the requirements of IEC 61131-2 in terms of shipping and
storage conditions. The following information applies to modules that are shipped and/or
stored in their original packaging.
Table 12- 6 Shipping and storage conditions for modules
Type of condition
Permissible range
Free fall (in shipping package)
≤1 m
Temperature From -40 °C to +70 °C
Barometric pressure from 1140 hPa to 660 hPa (corresponds to an altitude of
-1000 m to 3500 m)
Relative humidity 5% to 95%, without condensation
Sinusoidal vibrations according to
IEC 60068-2-6
5 - 8.4 Hz: 3.5 mm
8.4 - 500 Hz: 9.8 m/s
2
Shock according to IEC 60068-2-27
250 m/s
2
, 6 ms, 1000 shocks