Here you make the settings for for the SNMP agent on the CP, see section SNMP
(Page 54).
●
See section Certificate manager (Page 55).
In the global security settings among other things you will find the following parameter group:
●
Here you configure the VPN communication, refer to the section VPN (Page 58).
●
Here you configure the users, roles and rights for the TeleService access, refer to the
section Auto-Hotspot.
Configuration of the TeleService access (Page 63)
In the "CP identification" parameter group, you configure the following information for
authenticating the CP with the telecontrol server:
● Project number
The project number is the same for all telecontrol CPs in a STEP 7 project. TCSB
evaluates project numbers from 1 ... 2000.
If you change the project number, this parameter is changed for all CPs in the STEP 7
project.
● Station number
For each S7-1200 station with a telecontrol CP, an individual station number is
configured. TCSB evaluates station numbers from 1 ... 8000.
● Telecontrol password
Password for the authentication of the CP on the telecontrol server
8 ... 29 characters of the ASCII character set 0x20...0x7e
The password can be the same for all CPs of the STEP 7 project. The same password is
configured in TCSB for this station.
● Access ID
The displayed Access ID is formed from the hexadecimal values of project number,
station number and slot. The parameter of the type DWORD is allocated as follows:
– Bits 0 - 7: Slot
– Bits 8 to 20: Station number
– Bits 21 to 31: Project number