Technical data
10.5 Monitoring and response times of the DM-F Local fail-safe digital module
SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
101
10.5
Monitoring and response times of the DM-F Local fail-safe digital
module
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Table 10- 7 Monitoring and response times of the DM-F LOCAL fail-safe digital module
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Make time (with automatic start)
50 ms (typ.)
100 ms (max.)
Make time (with automatic start) after power failure
8.0 s (typ.)
8.2 s (max.)
Make time (monitored start)
50 ms (typ.)
100 ms (max.)
Off-delay in case of power failure
DC: 60 ms (typ.)
AC: 200 ms (typ.)
Off-delay after opening of the safety circuits
50 ms (typ.)
Recovery time after opening of the safety circuits
250 ms (typ.)
Recovery time after power failure
8.0 s (typ.)
Pulse duration
Sensor circuit: 30 ms (min.)
Start input 0.2 s (min.)
Cascading input: 0.2 s (min.)

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals