Technical data
10.5 Monitoring and response times of the DM-F Local fail-safe digital module
SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
101
Monitoring and response times of the DM-F Local fail-safe digital
module
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Table 10- 7 Monitoring and response times of the DM-F LOCAL fail-safe digital module
Monitoring and response times of the DM-F LOCAL fail-safe digital module
Make time (with automatic start)
• 50 ms (typ.)
• 100 ms (max.)
Make time (with automatic start) after power failure
• 8.0 s (typ.)
• 8.2 s (max.)
Make time (monitored start)
• 50 ms (typ.)
• 100 ms (max.)
Off-delay in case of power failure
• DC: 60 ms (typ.)
• AC: 200 ms (typ.)
Off-delay after opening of the safety circuits
Recovery time after opening of the safety circuits
Recovery time after power failure
• Sensor circuit: 30 ms (min.)
• Start input 0.2 s (min.)
• Cascading input: 0.2 s (min.)