EasyManuals Logo
Home>Siemens>Control Unit>SIMOCODE pro

Siemens SIMOCODE pro Manual

Siemens SIMOCODE pro
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
Technical data
10.2 Technical data of the DM-F Local fail-safe digital module
96
SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
10.2
Technical data of the DM-F Local fail-safe digital module
Technical data of the DM-F Local fail-safe digital module
Table 10- 2 Technical data of the DM-F Local fail-safe digital modules
LED
Status
Meaning
READY
Off
System interface not connected/supply voltage too low/device defective
Green
Device ON/system interface OK
Flashing green
Device ON/system interface not active or not OK
DEVICE
Off
Supply voltage too low
Green
Device ON
Flashing green
Self-test
Yellow
Configuration mode
Flashing yellow
Configuration error
Red
Device defective or faulty
OUT
Off
Safety-related output not active
Green
Safety-related output active
Flashing green
Feedback circuit not closed although start condition satisfied
IN
Off
Input not active
Green
Input active
Flashing green
Fault detected (e.g. cross-circuit at input, sensor simultaneity not satisfied)
SF
Off
No group fault
Red
Group fault (wiring error, cross-circuit, configuration error)
Flashing red
Group fault (feedback circuit fault, simultaneity condition not satisfied)
1
Off
Cross-circuit detection Off
Yellow
Cross-circuit detection On
Flashing yellow
Configuration mode, waiting for confirmation
Flickering yellow
Configuration error
2
Off
NC contact/NO contact
Yellow
NC contact/NC contact
Flashing yellow Configuration mode, waiting for confirmation
Flickering yellow Configuration error
3
Off
2 x 1-channel
Yellow
1 x 2-channel
Flashing yellow
Configuration mode, waiting for confirmation
Flickering yellow
Configuration error
4
Off
Debouncing time Y12, Y22, Y34 ~ 50 ms
Yellow
Debouncing time Y12, Y22, Y34 ~ 10 ms
Flashing yellow
Configuration mode, waiting for confirmation

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals