SIMOCODE pro - Fail-Safe Digital Modules
Manual, 11/2017, NEB631679702000/RS-AA/002
93
Technical data of the DM-F Local and DM-F PROFIsafe fail-safe
digital modules
Technical data of the DM-F Local and DM-F PROFIsafe fail-safe digital modules
Table 10- 1 Technical data of the DM-F Local and DM-F PROFIsafe fail-safe digital modules
Snap-mounted onto 35 mm DIN rail or screw-mounted using additional push-in
lugs
For connection to
• a basic unit
• another expansion module
• a current measuring module or current/voltage measuring module
• the operator-control block
Permissible ambient temperature
In operation -25 °C ... +60 °C
During storage and
-40 °C ... +80 °C
At installation altitude above sea level
≤ 2000 m
Max. +50 °C (no protective separation)
Max. +40 °C (no protective separation)
Degree of protection (according to
IEC 60529)
IP 20
Shock resistance (sine pulse)
EMC interference immunity
in
IEC 60947-5-1, Edition 3.1:2009, SN 27095:2006, IEC 61326-3-1:2008,
Rated control supply voltage U
s
according to DIN EN 61131-2
110 V - 240 V AC/DC,
24 V DC
• 24 V DC: 0.8 to 1.2xU
s
• 110 V to 240 V AC/DC: 0.85 to 1.1xU
s