Interfaces
3.5 Digital I/Os
SIMOTION D4x5-2
58 Manual, 02/2012
3.5 Digital I/Os
3.5.1 Properties
Interface characteristics
The digital I/Os on the X122, X132 and X142 connectors are for the connection of sensors
and actuators.
Table 3- 9 Wiring of X122, X132 and X142
Characteristics Type
Connector type Mini Combicon
Connectable cable types and
conductor cross-sections
Rigid
Flexible
Flexible with end sleeve
AWG
0.2 mm
2
to 1.5 mm
2
0.2 mm
2
to 1.5 mm
2
0.25 mm
2
to 1.5 mm
2
24 to 16
Stripped length 10 mm
Tool Screwdriver 0.4 x 2.0 mm
Max. cable length 30 m
Max. current carrying capacity
(ground)
8 A
Position of connectors
The following figure shows the position of the interface connectors on the D4x5-2 and the
distribution of the various digital I/Os.















'LJLWDOLQSXWV
SLQV
'LJLWDOLQSXWV
GLJLWDORXWSXWV
SLQV
DQG
SLQV
'LJLWDOLQSXWV
GLJLWDORXWSXWV
SLQV
SLQV
SLQV
SLQV
;; ;
Figure 3-5 Position of the X122, X132 and X142 digital interfaces (example of SIMOTION D445-2 DP/PN)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION D445-1 and is the answer not in the manual?

Siemens SIMOTION D445-1 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION D445-1
CategoryControl Unit
LanguageEnglish

Related product manuals