Technical data of the D4x5-2
5
5.1 Shipping and storage conditions
Transportation and storage conditions
The following conditions apply to modules that are shipped and stored in the original
packaging.
Table 5-1
Transportation conditions
Type of condition Permissible range/class
Transport Long-term storage
Climate class 2K4 according to
EN 60721‑3‑2:1997
1K4 according to
EN 60721‑3‑1:1997
Temperature From -40° C to +70° C From -25° C to +55° C
Relative humidity From 5 to 95% From 10% to 100%
Height Max. 4000 m above sea level,
For SINAMICS S120 drive components, see SINAMICS Manuals.
Atmospheric pressure ● > 620 hPa
●
< 1060 hPa
The specified values apply to a
transportation altitude of up to
4,000 m
● > 620 hPa
● < 1060 hPa
The specified values apply to a
storage altitude of up to 4,000 m
Biological environmental
conditions
Class 2B1 according to
EN 60721‑3‑2:1997
Class 1B1 acc. to
EN 60721‑3‑1:1997
Chemically active
environmental conditions
Class 2C2 according to
EN 60721‑3‑2:1997
Class 1C2 according to
EN 60721‑3‑1:1997
Shipping backup batteries
Backup batteries may only be shipped in the original packaging. No special authorization is
required to ship backup batteries. The lithium content of the backup battery is approximately
300 mg.
Note
The backup battery is classified as a hazardous substance, Class 9 in accordance with the
relevant air-freight transportation regulations.
Notes on handling backup batteries, see Replacing the battery in the fan/battery module
(Page 99
).
SIMOTION D4x5-2
Manual, 04/2014 77