01.2000 First Start-up
Siemens AG 6SE7087-6KP50
SIMOVERT MASTERDRIVES Operating Instructions 3-1
3 First Start-up
After removing the packaging, check that the unit is
intact and undamaged. Only intact units may be started
up. Please also check that the unit is complete, that the
correct optional boards are fitted, and that the
technology option has been released, if ordered.
Unpack and check the
units
See section
"Transport,
Storage,
Unpacking"
Retrofit any optional boards which have not yet been
installed, if necessary. Then install the units taking into
account the requirements at the point of installation and
the EMC instructions.
Mount the unit and
install optional boards
which have not yet
been fitted
See section
"Installation"
and "Installation
in Conformance
with EMC
Regulations"
If the DC link of the unit was de-energized for more than
one year, you have to newly form the DC link capacitors
Form the DC link
capacitors, if necessary
See section
"Forming"
Please connect, starting with the protective conductor,
the power cables or DC link buses and, if present, the
external 24 V supply. Pay attention to EMC instructions
when laying the cables. Please do not at this stage
connect any control, communication, encoder and motor
cables (exception: cable for connecting up an OP1S, if
parameterization is to be effected via the OP1S).
Connect the protective
conductor, the power
cables or buses and, if
present, the ext. 24 V
supply
See section
"Connecting-up"
and
"Installation in
Conformance
with EMC
Regulations"
Please connect the remaining control, communication,
encoder and motor cables. Pay attention to the EMC
instructions when laying the cables.
CAUTION
The encoder connector may
not
be
plugged in or unplugged with the power
on!
Connect the control
cables, communication
cables, encoder cables
and motor cables
See section
"Connecting-up"
and "Installation
in Conformance
with EMC
Regulations"
After checking that the cabling has been correctly
connected and that it sits properly, power up the
external 24 V supply or the line voltage. After the
electronics power supply has been started, the unit
initializes itself. The action can take several seconds.
The drive status is subsequently shown on the PMU.
Power up the external
24 V supply or the line
voltage
111
If the PMU does not show status °005 after completion
of the unit initialization, or if the unit has already been
parameterized before, you should carry out a parameter
reset to factory setting.
If necessary, carry out
parameter reset to
factory setting
See section
"Parameterization"