10.99 Parameterization
Siemens AG 6SE7087-6KP50
SIMOVERT MASTERDRIVES Operating Instructions 8-9
8.3 Parameter reset to factory setting
The factory setting is the defined initial state of all parameters of a unit.
The units are delivered with this setting.
You can restore this initial state at any time by resetting the parameters
to the factory setting, thus canceling all parameter changes made since
the unit was delivered.
Menu selection "Fixed settings"
P366 = ?
P970 = 0
Start parameter reset
0: Parameter reset
1: No parameter change
P060 = 2
Select desired factory setting
0: Standard
Note: This parameter was correctly set prior to despatch of
the unit and only needs to be changed in exceptional
cases.
P053 = 6
Grant parameter access
6: Parameter changes permitted via PMU and serial interface
SCom1 (OP1S and PC)
Unit carries out parameter
reset and goes into status
5 "Drive setting".
Fig. 8-4 Sequence for parameter reset to factory setting