Operating Instructions SIPLUS CMS4000 IFN AI-D
SIPLUS CMS4000 IFN AI-D
Operating Instructions, 07/2021, A5E32612781A-AB
24
5.1.4 UIK (Unique Identification Key)
The UIK is a clear, device dedicated identification/address. It is printed on the UIK label
plate and deposited in the firmware of the IFN AI-D. The device is addressed with the
UIK.
In order to communicate with the IFN AI-D, the UIK must be dedicated during the pa-
rameterization in X-Tools (see manual „SIPLUS CMS X-Tools reference manual“).
5.2 Diagnosis via LED-Indicator
Name PWR
Description power Indicator
Color green
Condition off no operation voltage
blinks firmware operates
Name ERR
Description error Indicator
Color red
Condition off no error
on error
Name LNK
Description indicator for connection to the controller
Color yellow
Condition off no connection to the controller
on connection to the controller established
blinks data exchange with the controller
Name CH1-6
Description error indicator for sensor input CH1-CH6
Color red
Condition off channel is not over parameterization on or no error
blinks sensor cable break